Honeywell
Honeywell Automatic Programming Control 120VAC 50/60Hz RM7850-A-1019
Honeywell Automatic Programming Control 120VAC RM7850-A-1019 is a cutting-edge solution tailored for industrial control systems. Engineered with precision and reliability in mind, this control unit plays a crucial role in optimizing processes with its automatic programming capabilities. Operating at 120VAC, the RM7850-A-1019 ensures seamless integration into diverse industrial electrical setups, providing efficient and intelligent control for enhanced performance.
Designed to meet the demanding requirements of industrial automation, the Honeywell Automatic Programming Control stands out with its advanced features. The unit's 135-degree split point enhances precision during programming, reducing errors and ensuring accurate control. With a focus on reliability, the RM7850-A-1019 is a key component for industrial applications, offering a robust and dependable solution for automated systems in diverse settings.
Honeywell Automatic Programming Control 120VAC 50/60Hz RM7850-A-1019 Features:
-
Access for external electrical voltage checks.
-
Application flexibility and communication interface capability.
-
Five LEDs provide sequence information.
-
Five function Run/Test Switch.
-
Interchangeable plug-in amplifiers.
-
Local or remote annunciation of operation and fault information (optional).
-
Nonvolatile memory retains history files and lockout status after loss of power.
- Compatible with existing Honeywell flame detectors.
- Application: Programming Control
- Dimensions (mm): 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase
-
Comments: LHL-LF&HF Proven
-
Frequency: 50 Hz; 60 Hz (±10%)
-
Voltage: 120 Vac (+10, -15%)
-
Shipping and Storage Temperature Range (F): -40 F to +140 F
-
Shipping and Storage Temperature Range (C): -40 C to +60 C
-
Approvals, Federal Communications Commission: FCC Part 15, Class B, Emissions.
-
Flame Establishing Period – Pilot: 3 sec or 5 sec
-
Flame Establishing Period – Main: 3 sec, or 5 sec, or Intermittent
-
Interlocks: Lockout
-
Preignition: Yes
-
PrePurge: Determined by ST7800A Purge Timer Card
-
PostPurge: 15 sec
-
Required Components: Q7800A,B Universal Wiring Subbases. R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card.
-
AirFlow Check: User selectable
-
Second Stage Pilot Valve: Intermittent
-
Pilot Type: interrupted
-
Vibration: 0.5 G environment
-
Approvals, Swiss RE: Acceptable
-
Approvals, Factory Mutual: Report No. J.I. OYOA9.AF.
-
European Directives: Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC).
-
Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved to EN298.